Formula sheet
AC Power Formula Sheet
AC power formulas for RMS values, phasors, impedance, power factor, energy, three-phase and unbalanced circuits, voltage drop, harmonics, fault current, and correction.
This formula sheet collects common relationships used in introductory AC power analysis. It assumes sinusoidal steady-state operation unless stated otherwise. For transients, faults, harmonics, saturation, switching converters, and unbalanced systems, these equations must be extended or replaced by the appropriate time-domain or sequence-domain model.
Design-case selection
Use formulas against a named operating case, not in isolation. A compact design table should include:
Useful screening quantities are:
For multiple parallel units where one largest unit may be unavailable, a simple N-1 firm apparent-power capacity is:
This expression checks capacity only. It does not prove protection coordination, equal load sharing, cooling adequacy, physical separation, or maintainability.
Sinusoidal quantities
For a sinusoidal voltage:
Angular frequency is:
For an ideal sine wave:
Peak-to-peak voltage is:
Always state whether a value is RMS, peak, or peak-to-peak. Power-system voltages and currents are normally RMS values.
Phasor and impedance relations
For sinusoidal steady-state analysis:
Impedance is:
Admittance is:
Inductive reactance:
Capacitive reactance:
Impedance magnitude and phase:
Use the two-argument arctangent so the phase remains in the correct quadrant. These formulas apply to linear components at one frequency. They do not describe nonlinear loads, saturation, or harmonic spectra by themselves.
Single-phase power
For sinusoidal voltage and current with phase angle \phi:
Complex power:
Apparent power magnitude:
For purely sinusoidal voltage and current:
If current is non-sinusoidal, total power factor is still P/S, but it may not equal the displacement power factor of the fundamental component.
Balanced three-phase power
For a balanced three-phase system:
where V_{LL} is line-to-line RMS voltage and I_L is line current.
For a wye-connected balanced load:
For a delta-connected balanced load:
Balanced formulas are not valid for unbalanced loads unless each phase is analysed separately or symmetrical components are used.
Unbalanced Phase Screening
Total active power from phase quantities:
Total reactive power:
Neutral current from phase-current phasors:
Voltage unbalance percentage:
Unbalanced checks should identify phase loading, neutral current, grounding path, single-phase loads, harmonic triplen currents, and protection assumptions.
Current from power
Single-phase current from active power:
Balanced three-phase line current:
Current from apparent power:
for single-phase systems, and:
for balanced three-phase systems.
These equations explain why low power factor increases current for the same delivered active power.
Energy and Demand
Energy over time:
Average power:
Demand factor:
Energy and demand checks should state billing interval, duty cycle, metering location, diversity assumptions, power factor, and whether demand is peak, average, or contractual.
Losses and voltage drop
Resistive loss:
Approximate single-phase voltage drop:
Approximate balanced three-phase line-to-line voltage drop:
The signs of the reactive term depend on load power factor and the reference convention. For accurate design, use the governing standard, conductor temperature, actual route length, grouping factors, harmonic loading, and supply impedance.
Power factor correction
Reactive compensation needed to move from initial power factor PF_1=\cos\phi_1 to target power factor PF_2=\cos\phi_2 at active power P:
For a three-phase capacitor bank with line-to-line RMS voltage V_{LL}:
for a wye-connected bank, and:
for a delta-connected bank.
These formulas assume balanced sinusoidal operation. Check switching steps, overcorrection, resonance, harmonic distortion, discharge resistors, voltage rating, and protection before specifying a capacitor bank.
Transformer and equipment loading
Apparent power rating:
for single phase, and:
for balanced three phase.
Active power available at a given power factor:
A transformer loaded to 100 kVA can deliver 100 kW at unity power factor but only 80 kW at power factor 0.8, while carrying the same apparent loading.
Equipment utilization for a design case:
Remaining apparent-power margin:
For load growth from present apparent power S_0 to future apparent power S_f:
These equations should be evaluated for normal operation, emergency loading, ambient-temperature derating, harmonic heating, and maintenance states. A positive margin in normal operation may disappear when one transformer, feeder, or cooling path is unavailable.
Per-Unit and Base Quantities
Three-phase base current:
Single-phase base current:
Three-phase base impedance:
Per-unit impedance:
Percent impedance:
Per-unit values simplify transformer, cable, motor, and fault studies, but bases must be stated clearly whenever voltage level or apparent-power base changes.
Fault Current Screening
Approximate single-phase short-circuit current:
Approximate balanced three-phase short-circuit current:
Short-circuit apparent power:
Transformer-limited fault current from percent impedance:
These screening equations do not replace protection coordination. Check available fault current, X/R ratio, breaker interrupting rating, let-through energy, grounding method, arc-flash assumptions, and upstream/downstream selectivity.
Mini example: transformer-limited fault current
A 10 MVA transformer feeds a 13.8 kV bus and has 5.75% impedance. Rated line current is:
Transformer-limited short-circuit current is approximately:
This is a first screen. A complete study also checks upstream source strength, cable impedance, motor contribution, parallel transformers, grounding, X/R ratio, and source modes with generators, UPS systems, or battery converters.
Harmonic checks
Total harmonic distortion of current is commonly expressed as:
where I_1 is fundamental RMS current and I_2, I_3, \ldots are harmonic RMS currents.
Total RMS current is:
Harmonic current increases heating even when it does not increase useful power. Neutral conductors, transformers, capacitor banks, and protective devices may need special evaluation when harmonic content is significant.
Mini example: three-phase load current
A balanced three-phase motor load requires:
at:
with:
The line current is:
Substitute:
If the power factor were improved to 0.96 for the same active power and voltage:
The active power is unchanged, but current and associated I^2R losses are lower. A full design would still check motor starting, cable rating, voltage drop, protection coordination, harmonics, and duty cycle.
Validation notes
For calculation records, state:
- whether values are RMS, peak, phase, line-to-line, or line-to-neutral;
- whether the model assumes balanced, sinusoidal, steady-state operation;
- voltage level, frequency, grounding method, and source mode;
- power factor convention and sign convention for reactive power;
- conductor temperature, cable route length, grouping, and installation assumptions;
- transformer impedance, source impedance, and fault-current contribution assumptions;
- metering location and whether demand is instantaneous, interval-averaged, or contractual;
- acceptance criteria for current, voltage drop, harmonic distortion, equipment loading, and protection operation.
The calculation is not complete until the result is linked to a rating, limit, measurement, or operating decision.
Common cautions
Do not use balanced three-phase equations for unbalanced systems without checking phase quantities. Do not size equipment from kW alone when power factor or harmonic current is important. Do not add power factor correction capacitors without checking resonance and light-load overvoltage. Do not treat RMS, peak, and peak-to-peak values as interchangeable. Do not assume that a breaker can interrupt a fault simply because its continuous current rating is high enough.